MODELMAX LiFE ONLINE UPS 2KVA/48V

વર્ણન (Description):

  • INPUT CAPACITY: 2000VA / 1800W

  • INPUT VOLTAGE RANGE:

    • Low Line Transfer: 160VAC/140VAC/120VAC/110VAC ±3% (based on load 100%-80% / 80%-70% / 70%-60% / 60%-0%)

    • Low Line Comeback: 175VAC/155VAC/135VAC/125VAC ±3%

    • High Line Transfer: 300VAC ±3%

    • High Line Comeback: 290VAC ±3%

  • INPUT PARAMETERS: Single Phase with Ground, Frequency 40Hz - 70Hz, Power Factor >0.99, THD(i) >5% @ 205-245VAC.

  • OUTPUT VOLTAGE: 200*/208*/220/230/240 VAC (Regulation ±1%)

  • OUTPUT FREQUENCY: Synchronized (47-53Hz / 57-63Hz), Battery Mode (50Hz ±0.1% or 60Hz ±0.1%)

  • OUTPUT PERFORMANCE:

    • Current Crest Ratio: 3:1 (Max)

    • Harmonic Distortion: <1% THD (Linear Load), <4% THD (Non-Linear Load)

    • Wave Form: Pure Sine Wave

  • TRANSFER TIME:

    • AC/DC: Zero

    • Inverter to Bypass: 4ms (Typical)

    • ECO to Battery: 8ms (Typical), 10ms (Max)

  • OVERLOAD CAPACITY:

    • Online Mode: 100% (+4sec) @ <40°C or 2.5min (+4sec) @ >=40°C; 130% (+1sec), 140% (+0.5sec)

    • Inverter Mode: 100% (+4sec) @ <40°C or 1min (+4sec) @ >=40°C; 130% (+1sec), 140% (+0.5sec)

  • EFFICIENCY: ECO Mode <96%, AC Mode <90%, Battery Mode <88%

  • BATTERY SYSTEM:

    • Nominal Voltage: 48V

    • Charging Current: 20A Max (Adjustable: 2/4/8/10/12/14/16/20A via LCD)

    • Charging Voltage: 53.3VDC ±1% (Adjustable)

    • Charging Profile: CC-CV; Ripple Current <8%

  • INDICATION & ALARMS:

    • LCD Indicators: Load Level, Battery Level, AC/Battery/Bypass Mode, Fault.

    • Alarms: Battery Mode (every 5sec), Low Battery (every 2sec), Overload (every 1sec), Fault (Continuously).

  • PHYSICAL SPECIFICATIONS:

    • Dimensions: 530 x 145 x 220 mm

    • Net Weight: 8.6 Kgs

  • ENVIRONMENT: 20-95% RH (Non-Condensing), Temp 0-45°C, Noise Level <53dBa @ 1 meter.

  • MANAGEMENT:

    • Standard: Smart RS-232 / USB (Supports Windows, Linux, Mac)

    • Optional: SNMP (Web-based power management)

  • True Double-Conversion.Microprocessor Control Optimizes Reliability.
  • Comprehensive Display allows easy monitoring and access of UPS status.
  • Advanced Battery Management (ABM).
  • High Power Factor Charger upto 1000W Capacity with very Low Ripple Current when Charging Battery.
  • Lithium-ion Battery Compatiable.
  • Low input THDi (5%) to reduce Power system pollution.
  • Output power Factor is 0.9.

User Manual

Complete user manual for product usage and settings.