MAX LIFE ONLINE UPS 1KVA - ( 1000VA / 900W )
(MICROTEK)
INPUT CAPACITY: 1000VA / 900W
INPUT VOLTAGE RANGE:
Low Line Transfer: 160VAC/140VAC/120VAC/110VAC ±3% (based on load 100%-80% / 80%-70% / 70%-60% / 60%-0%)
Low Line Comeback: 175VAC/155VAC/135VAC/125VAC ±3%
High Line Transfer: 300VAC ±3%
High Line Comeback: 290VAC ±3%
INPUT PARAMETERS: Single Phase with Ground, Frequency 40Hz - 70Hz, Power Factor >0.99, THD(i) >5% @ 205-245VAC.
OUTPUT VOLTAGE: 200*/208*/220/230/240 VAC (Regulation ±1%)
OUTPUT FREQUENCY: Synchronized (47-53Hz / 57-63Hz), Battery Mode (50Hz ±0.1% or 60Hz ±0.1%)
OUTPUT PERFORMANCE:
Current Crest Ratio: 3:1 (Max)
Harmonic Distortion: <1% THD (Linear Load), <4% THD (Non-Linear Load)
Wave Form: Pure Sine Wave
TRANSFER TIME:
AC/DC: Zero
Inverter to Bypass: 4ms (Typical)
ECO to Battery: 8ms (Typical), 10ms (Max)
OVERLOAD CAPACITY:
Online Mode: 100% (+4sec) @ <40°C or 2.5min (+4sec) @ >=40°C; 130% (+1sec), 140% (+0.5sec)
Inverter Mode: 100% (+4sec) @ <40°C or 1min (+4sec) @ >=40°C; 130% (+1sec), 140% (+0.5sec)
EFFICIENCY: ECO Mode <96%, AC Mode <89%, Battery Mode <88%
BATTERY SYSTEM:
Nominal Voltage: 48V
Charging Current: 20A Max (Adjustable: 2/4/8/10/12/14/16/20A via LCD)
Charging Voltage: 53.3VDC ±1% (Adjustable)
Charging Profile: CC-CV; Ripple Current <8%
INDICATION & ALARMS:
LCD Indicators: Load Level, Battery Level, AC/Battery/Bypass Mode, Fault.
Alarms: Battery Mode (every 5sec), Low Battery (every 2sec), Overload (every 1sec), Fault (Continuously).
PHYSICAL SPECIFICATIONS:
Dimensions: 397 x 145 x 220 mm
Net Weight: 6.4 Kgs
ENVIRONMENT: 20-95% RH (Non-Condensing), Temp 0-45°C, Noise Level <53dBa @ 1 meter.
MANAGEMENT:
Standard: Smart RS-232 / USB (Supports Windows, Linux, Mac)
Optional: SNMP (Web-based power management)