Technical Specification

Listed

• LPCB

Certified

• EN54-2:1997 + A1:2006
• EN54-4:1997 + A1:2002 + A2:2006


Control Panel

Input Voltage
• 240VAC ±10% / -15%, 50/60Hz

Input Current Consumption
• 1A

PSU Output to CIE
• 24.5 to 28.5VDC

Batteries
• 2 × 12V / 24Ah

Memory (Non-Volatile)
• 1000 Fire Events
• 10,000 General Events

Zones
• 3,000 Programmable

Groups
• 3,000 Programmable

Programmable Relays
• 4 Circuits (Normally Open/Close)

Programmable Input
• 1 Circuit (Power Limited 24VDC – For Future Use)

Programmable Auxiliary Power
• 19 to 28VDC (Current Limited)

Fixed Outputs (FPE / Sounder)
• 2 Circuits (18 to 28VDC, Current Limited)

Indicator
• 24 LED Status
• 160 Zone Indicators

Display
• 7" TFT Touch Screen

Keypad
• 5 Brigade Buttons
• Programming Keypad


Physical

Material / Color
• Flat Sheet Metal
• Outer Glass Door
• Orange Stripe

Dimensions (L × W × H)
• 530 × 490 × 135 mm

Weight
• 16.70 kg (4 Loop Panel)

Humidity
• 0 to 95% Relative Humidity
• Non-Condensing


Loop Specifications

Protocol / Addressing
• Agni Addressing
• Value Range: 1 to 254

No. of Loop
• 4 Loops
• 254 Devices per Loop

Protection
• Built-in 4kV Surge Protection

Power Rating
• 16 to 24VDC / 500mA

Cable Specification
• Maximum Cable Length: 1.2 km
• 2 × 1.5mm² Solid Core Fire Resistance Cable


Networking and Interfaces

Panel to Panel Communication
• CAN Bus (Loop)

Number of Panels
• 512 Units

Interface Port
• USB
• RS485 Serial
• RS232 Serial
• Ethernet

 

Features and Benefits

Certification
• EN54-2:1997 + A1:2006, EN54-4:1997 + A1:2002 + A2:2006 Certified

Approval
• LPCB Approved

Microprocessor Technology
• Using advanced microprocessor technology with large memory capacity

User Interface
• Enhanced user interface combining LCD Touch Screen and keypad access

Visual Algorithm
• Supports real-time visual algorithm

False Alarm Prevention
• Enhanced false alarm prevention

Programming
• Keypad and PC programming

Communication Interface
• Built-in multiple interface protocols such as USB, Ethernet, CAN Bus, Serial and RS485 (Available only in FL-4004/4 Panel)

Loop Powered Devices
• Supports loop-powered devices for extra savings on cable cost

Printer & LED Indicators
• Built-in Printer and 160 LED Zone Indicators


Commissioning Advantages and Capacity

Auto Enrolling
• Auto enrolling of devices

Loop Mapping
• Loop mapping with color coding status

Device Monitoring
• Monitor device mismatch and dual address conflict

Command Builder
• Command Builder to create requirements for fire event scenarios

Loop Protection
• Loop protection against power surge

Sounder Programming
• One-man test with ON/OFF sounder programming protection

Network Application
• Maximum 4 loops in network application with built-in 4-in-1 communication card

Devices Per Loop
• Supports 254 devices per loop

Standalone Capacity
• Maximum 6 loops in standalone basis (1,524 devices)

Network Capacity
• Network up to 512 Nodes

Programmable Capacity
• Programmable Capacity

Zones
• Up to 3000 Zones

Sounder Groups
• Sounders Groups 1–1000

Module Groups
• Modules Groups 1001–2000

LED Zone Indicators
• Built-in 160 LED Zone Indicators